Independent reference. Not a government website. Guidance, not engineering advice: confirm with your fire marshal.

California · city · ERRCS / BDA requirements

ERRCS and BDA requirements in Los Angeles, California

LAFD Requirement #105 applies to new buildings where radio signal is below code levels and the building has more than 3 stories above grade, 50,000 sq ft or more in total, a basement of 10,000 sq ft or more, any level 2 or more stories below grade, or 20,000 sq ft or more with a solar photovoltaic system. Group R-3 is excepted. Existing buildings meeting those conditions are covered when their fire alarm system is replaced.

Last verified Updated Confidence medium2 sourcesChangelog

Guidance, not engineering advice. Rules on this page come from the documents listed under Sources. Confirm with Los Angeles Fire Department, Fire Prevention and Public Safety Bureau before you design, permit or test a system.

Who must comply

State rules apply here too. See California statewide rules.

RuleEffectCitationSource
Group R-3 occupancies are excepted.Not requiredLAFD Requirement #105, Applicability (Exception)Los Angeles Fire Department
New buildings with more than 3 stories above grade plane must have radio coverage where signal levels are below code.Must meetLAFD Requirement #105, Applicability 1Los Angeles Fire Department
New buildings with a total building area of 50,000 sq ft or more must have radio coverage where signal levels are below code.Must meetLAFD Requirement #105, Applicability 2Los Angeles Fire Department
New buildings of 20,000 sq ft or more that have a solar photovoltaic system are covered.NoteLAFD Requirement #105, Applicability 5Los Angeles Fire Department
New buildings with a basement of 10,000 sq ft or more, or any level 2 or more stories below grade, are covered.AHJ may requireLAFD Requirement #105, Applicability 3-4Los Angeles Fire Department
Existing buildings meeting the new-building conditions are covered when the building's fire alarm system is replaced.AHJ may requireLAFD Requirement #105, Applicability (Section 510.2)Los Angeles Fire Department
TriggerPublished value
Minimum building size50,000 sq ft
Minimum stories4
Height triggerNot published; confirm with the fire marshal
Below-grade areasTrue
Building types namedNot published; confirm with the fire marshal
Existing buildings must retrofitNot published; confirm with the fire marshal
Compliance deadlineNot published; confirm with the fire marshal

Requirement #105 is dated August 7, 2018 and interprets the 2016 California Fire Code and 2017 Los Angeles Fire Code. LAFD's requirements page still lists it as updated. Later code editions may change details; confirm with LAFD.

RequirementValue
Minimum downlink signalNot published; confirm with the fire marshal
Minimum uplink signalNot published; confirm with the fire marshal
Delivered audio quality (DAQ)Not published; confirm with the fire marshal
Coverage, general areas90% of floor area
Coverage, critical areas99% of floor area
Critical areas namedFire command centers, Fire pump rooms, Exit stairs, Exit passageways, Elevator lobbies, Standpipe cabinets, Sprinkler valve locations, Other areas LAFD deems critical
Public safety radio bandsLAFD 800 MHz, analog conventional repeat mode (856.2375-860.9375 MHz and 811.2375-815.9375 MHz)

LAFD lists its assigned uplink and downlink frequency pairs and nine simulcast transmitter sites in the requirement, and keeps the current list for designers and Regulation No. 4 testers. Signal boosters must handle analog and digital at the same time. Riser cables go in conduit with 1-hour or 2-hour pathway survivability depending on the stair enclosure rating.

Testing

TestWhat the source saysSource
Acceptance testLADBS Electrical Inspection signs the pre-test sheet first. Fire Development Services inspectors witness the final acceptance test, check the as-built drawings and link budget, and test the radio channels in all critical areas with spot tests elsewhere. Backup batteries are load tested.LAFD Requirement #105, Acceptance Test
Annual testAnnual testing is done by a person holding a valid LAFD Regulation No. 4 Certificate of Fitness for two-way radio communications enhancement systems, and reported on an LAFD-approved F-340R Fire Protection System Performance Report. A spectrum analyzer oscillation check is part of each annual inspection.LAFD Requirement #105, Annual Testing and Proof of Compliance; 510.5.3(7)
Five-year testNot published in the documents we read; confirm with the fire marshal.None found
Coverage assessment intervalNot published in the documents we read; confirm with the fire marshal.None found

Maintenance and monitoring

  • Service-affecting failure: a qualified technician evaluates within 24 hours, repairs are complete within five working days, and the owner notifies LAFD right away.
  • Non-service-affecting failure: evaluation the next business day and repairs within 15 business days.
  • Secondary power: a dedicated battery with at least 24 hours at 100% capacity, or a generator with 24 hours plus at least 2 hours of battery.
  • The owner pays to modify the system if LAFD frequencies change.

Source: Fire Prevention and Public Safety Bureau Requirement #105, Emergency Responder Radio System (ERRS) Coverage (dated August 7, 2018)

Permit and inspection process

  1. LAFD plan review and approval is required to install or modify the system. LAFD Requirement #105, Approval and Permit
  2. Submit detailed as-built drawings and an 800 MHz ERRS RF test before final inspection and the acceptance test. LAFD Requirement #105, Approval and Permit
  3. No amplifier that can interfere with LAFD frequencies may be installed without prior coordination and LAFD approval. LAFD Requirement #105, Non-Interference

Codes and standards referenced

Code or standardEditionSource
California Fire Code / Los Angeles Fire Code Section 5102016 CFC / 2017 LAFC (named in Requirement #105)s1
NFPA 72 Chapter 24, Section 24.5.2 (Two-Way Radio Communications Enhancement Systems)2016s1

Notes

Medium confidence: Requirement #105 dates from 2018 and cites the 2016 California Fire Code. LAFD still links this 2018 document as "Requirement #105 (Updated)" on its requirements page, and publishes it only as an Issuu viewer, so we could not re-check the text with our tools in October 2026. Based on LAFD Requirement #105 (approved 8/7/2018); confirm the current version with LAFD.

Questions people ask

Who can do the annual ERRCS test in Los Angeles?

A person holding a valid LAFD Regulation No. 4 Certificate of Fitness in the two-way radio communications enhancement system category, reporting on form F-340R (LAFD Requirement #105).

How fast must a broken ERRCS be fixed in Los Angeles?

For a service-affecting failure, a technician evaluates within 24 hours and repairs are done within five working days, and the owner tells LAFD right away (LAFD Requirement #105, Maintenance).

Sources

Primary documents we read for this page. Rules change; confirm with your fire marshal (AHJ).